Below the menu navigation structure and MPS3000 default parameter settings.
Navigation
Set Page
Set Page
Set Page
Set Page
PAGE 0
PAGE 1
PAGE 2
PAGE 3
SYSTEM PARAMETER
*** SETTINGS ***
VOLTAGE
*** SETTINGS ***
CURRENT
*** SETTING S***
OVERLOAD
*** SETTINGS ***
SELECT
SELECT
SELECT
SELECT
PRESS KEYS TO CHANGE PARAMETER VALUE
LINE VOLTS (Vn)
480V
STAR TO DELTA AT
U/V LEVEL
80% OF Vn
MAX START TIME
10 SEC.
CURVE MULTIPLIER
6
LINE FREQUENCY
60Hz
CONFIG. OUTPUT A
TRIPPING / ALARM
U/V DELAY
5.0 SEC.
NUMBER OF STARTS
10
OVERLOAD PICKUP
105 % OF FLC
VT PRIMARY
VT NOT CONNECTED
OUTPUT DELAY
0 SEC.
UV ACTIVE AT STOP
DISABLE
STARTS PERIOD
30 MIN.
HOT/COLD RATIO
50 %
VT SECONDARY
VT NOT CONNECTED
CONFIG. OUTPUT B
TRIPPING / ALARM
U/V STRT PREVENT
OFF
START INHIBIT
15 MIN.
RUN COOL T CONST
10 MIN.
MOTOR FLC
100 AMP.
OUTPUT DELAY
0 SEC.
U/V AUTO RESTART
BOTH SUP. & Vin
U/C LEVEL 1
50 % OF FLC
STP COOL T CONST
30 MIN.
CT PRIMARY
100 AMP.
CONFIG. OUTPUT C
ALARM - FAIL SAFE
U/V RESTRT DELAY
4.0 SEC.
U/C LEVEL 1 DELAY
2 SEC.
UNBALANCE K FCTR
5
GND CT PRIMARY
100 AMP.
OUTPUT DELAY
0 SEC.
O/V LEVEL 1
115 % OF Vn
U/C LEVEL 2
40 % OF FLC
RTD BIAS
OFF
GND FAULT LEVEL 1
5% OF FLC
CONFIG. OUTPUT D
TRIP
O/V LEVEL 2
120 % OF Vn
U/C LEVEL 2 DELAY
5 SEC.
RTD BIAS MINIMUM
40 °C
G/F LEVEL 1 DELAY
10 SEC.
OUTPUT DELAY
0 SEC.
O/V LEVEL 2 DELAY
1 SEC.
LOAD INCREASE
120 % OF FLC
RTD BIAS MIDDLE
130 °C
GND FAULT LEVEL 2
10% OF FLC
CONFIG. INPUT A
AUTHORIZED KEY
O/C LEVEL 1 – JAM
400 % OF FLC
RTD BIAS MAXIMUM
155 °C
G/F LEVEL 2 DELAY
0.5 SEC.
CONFIG. INPUT B
EXT. FAULT 1
O/C LEVEL 1 DELAY
2.0 SEC.
THERMAL LEVEL 1
80 % OF CAPACITY
G/F DURING START
100% OF FLC
CONFIG. INPUT C
EXT. FAULT 2
O/C LEVEL 2 –
SHORT
800 % OF FLC
STALL TIME FCTR
50%
CURRENT INHIBIT
OFF
CONFIG. INPUT D
REMOTE RESET
O/C LEVEL 2 DELAY
0.5 SEC.
STARTING METHOD
DIRECT ON LINE
PROTECTION ONLY
YES
UNBALANCE LEVEL 2
15 % OF FLC