SET PAGE - MENUS
Page 36 of 67
Temperature Settings
Temperature
*** Settings ***
General Note:
Level 1 & 2 Fault
Display
Fault occurs when
temperature is above the set
parameter for more than a
fixed time period of 2
seconds
Description
RTD Type
Platinum 100
Ohm
Resistance Temperature Detector Type.
Range: Copper 10 Ohm, Platinum 100 Ohm, Nickel 120 Ohm
Sensor 7-10
Type
RTD
Type of sensors T7..T10. MPS3000 can be ordered with T7..T10
measurement circuits designed for Thermistors instead RTD.
Range: RTD, PTC Thermistor, NTC Thermistor
T1 Level 1
120 EC
RTD No. 1 level 1
Range: 0 - 250 EC. Increment: 1 EC
T1 Level 2
140 EC
RTD No. 1 level 2.
Range: 0 - 250 EC. Increment: 1 EC
T2 Level 1
120 EC
RTD No. 2 level 1
Range: 0 - 250 EC. Increment: 1 EC
T2 Level 2
140 EC
RTD No. 2 level 2
Range: 0 - 250 EC. Increment: 1 EC
T3 Level 1
120 EC
RTD No. 3 level 1
Range: 0 - 250 EC. Increment: 1 EC
T3 Level 2
140 EC
RTD No. 3 at level 2
Range: 0 - 250 EC. Increment: 1 EC
T4 Level 1
120 EC
RTD No. 4 level 1
Range: 0 - 250 EC. Increment: 1 EC
T4 Level 2
140 EC
RTD No. 4 level 2
Range: 0 - 250 EC. Increment: 1 EC
T5 Level 1
120 EC
RTD No. 5 level 1
Range: 0 - 250 EC. Increment: 1 EC
T5 Level 2
140 EC
RTD No. 5 level 2
Range: 0 - 250 EC. Increment: 1 EC
T6 Level 1
120 EC
RTD No. 6 level 1
Range: 0 - 250 EC. Increment: 1 EC
T6 Level 2
140 EC
RTD No. 6 level 2
Range: 0 - 250 EC. Increment: 1 EC