EasyManuals Logo

Solcon MPS 3000 User Manual

Solcon MPS 3000
67 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #34 background imageLoading...
Page #34 background image
SET PAGE - MENUS
Page 34 of 67
maximum
155 °C
capacity should be 100%.
Range: RTD Middle…250°C. Increment of: 1°C.
Thermal Level 1
80% of Capacity
Thermal Capacity level 1. Normally used for alarm indication.
Range: 50 - 99 % of maximum thermal capacity. Increments of : 1%
Stall Time Fact
50%
Stall Time Factor. The ratio between motor thermal time constant when speed switch
is closed (indicating slow speed) to thermal time constant with open speed switch -
(indicating high speed). Operative when speed switch is used.
Range: 20 - 100 %. Increments of: 1%