EasyManua.ls Logo

Sonel MPI-540 - Low-Voltage Measurement of Resistance; Measurement of Resistance; Measurement of Resistance of Protective Conductors and Equipotential Bonding with ±200 Ma Current

Sonel MPI-540
76 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MPI-540 ● MPI-540-PV BRIEF USER MANUAL
29
3.9 Low-voltage measurement of resistance
3.9.1 Measurement of resistance
Select item R
X
, to call up the
measurement screen.
Connect the meter to the tested
object.
Measurement starts automati-
cally.
During the measurement the
H.V./REC/CONT. diode is lit
green and a sound signal is
emitted.
NOTE!
Display of symbols indicates that the tested object is live. The
measurement is blocked. The meter must be immediately disconnected from the
object.
3.9.2 Measurement of resistance of protective conductors and equipoten-
tial bonding with ±200 mA current
Select item R
CONT
, to call up the
measurement screen.
Connect the meter to the tested
object.
Measurement starts automati-
cally.
NOTE!
Display of symbols indicates that the tested object is live. The meas-
urement is blocked. The meter must be immediately disconnected from the object.

Table of Contents

Other manuals for Sonel MPI-540

Related product manuals