MPI-540 ● MPI-540-PV – BRIEF USER MANUAL
8.1.4 Measurement of fault loop impedance Z
L-PE[RCD]
(without triggering of RCD)
Measurement of fault loop impedance Z
S
Test range according to IEC 61557-3:
0.50…1999 Ω for 1.2 m leads, WS-03 and WS-04
0.51...1999 Ω for 5 m, 10 m and 20 m leads
It will not trip RCDs of I
Δn
≥ 30 mA
Rated operating voltage U
n
: 110 V, 115 V, 127 V, 220 V, 230 V, 240 V
Operating voltage range: 95 V…270 V
Rated mains frequency f
n
: 50 Hz, 60 Hz
Operating frequency range: 45…65 Hz
Control of correctness of PE terminal connection by means of a touch electrode
8.1.5 Measurement of parameters of RCD
Measurement of RCDs type: AC, A, B, B+, F, EV
Rated operating voltage U
n
: 110 V, 115 V, 127 V, 220 V, 230 V, 240 V
Operating voltage range: 95 V…270 V
Rated mains frequency f
n
: 50 Hz, 60 Hz
Operating frequency range: 45…65 Hz
RCD trigger and response time test t
A
(for measurement function t
A
)
Test range according to IEC 61557-6: 0 ms ... to the upper limit of displayed value
Setting
of multi-
ple val-
ues
General type
▪ Short-time delay type
▪ AC module in EV type
0..300 ms (TN/TT)
0..400 ms (IT)
1)
for I
n
= 10 mA and 0.5 I
n
accuracy is ±(2% m.v. + 3 digits)
2)
for measurements acc. to IEC 62955
3)
for measurements acc. to IEC 62752
Accuracy of differential current setting:
for 1*I
n
, 2*I
n
, 5*I
n
..................................................................... 0..8%
for 0.5*I
n
.................................................................................... -8..0%