MPI-540 ● MPI-540-PV – BRIEF USER MANUAL
8.2.6 Measuring harmonics
DC, 1..40, grouping: harmonics sub-groups acc. to EN 61000-4-7
0.15% U
nom
if m.v.<3% U
nom
5% + 0,1% n) m.v. if m.v.≥ 3% U
nom
Depending clamps
used (see specifica-
tions for I
RMS
)
0.5% I
nom
if m.v.<10% I
nom
5% + 0,1% n) m.v. if m.v.≥ 10% I
nom
Voltage THD-F
(n = 2..40)
0.0…100.0%
for U
RMS
≥ 1% U
nom
current THD-F
(n = 2..40)
0.0…100.0%
for I
RMS
≥ 1% I
nom
8.2.7 Unbalance
Unbalance
(voltage and current)
Unbalance factor for positive, nega-
tive and zero sequence
0.0% ... 10.0%
for
80% U
nom
≤ U
RMS
< 150% U
nom
0.15%
(absolute uncertainty)
8.2.8 Power and energy measurement
Conditions
(for power and energy
80% U
nom
≤ U
RMS
< 120% U
nom
)
Active power
Active energy
2% I
nom
≤ I
RMS
< 5% I
nom
cos = 1
depending
on
U
nom
and I
nom
5% I
nom
≤ I
RMS
≤ I
nom
cos = 1
5% I
nom
≤ I
RMS
< 10% I
nom
cos = 0.5
10% I
nom
≤ I
RMS
≤ I
nom
cos = 0.5
Reactive power
Reactive energy
2% I
nom
≤ I
RMS
< 5% I
nom
sin = 1
depending
on
U
nom
and I
nom
5% I
nom
≤ I
RMS
< I
nom
sin = 1
5% I
nom
≤ I
RMS
< 10% I
nom
sin = 0.5
10% I
nom
≤ I
RMS
< I
nom
sin = 0.5
10% I
nom
≤ I
RMS
< I
nom
sin = 0.25
Apparent power
Apparent energy
depending
on
U
nom
and I
nom
0…1
50% U
nom
≤ U
RMS
< 150% U
nom
10% I
nom
≤ I
RMS
< I
nom
Displacement power
factor (cosφ/ DPF)
0…1
50% U
nom
≤ U
RMS
< 150% U
nom
10% I
nom
≤ I
RMS
< I
nom