EasyManua.ls Logo

Stober SC6 Series - Braking resistor; Tubular fixed resistor FZMU, FZZMU

Stober SC6 Series
96 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8 | Monitoring and diagnostics STOBER
48
02/2020 | ID 443025.06
§ L1X
• L10 = No Link
No connection to another EtherCAT device via X201 (OUT port)
• L11 = Link Detected
Connection to another EtherCAT device via X201 (OUT port)
** EtherCAT network connection – error counter
§ L0 xx = Link Lost Counter
Number of connection failures (hexadecimal) at X200 (IN port)
§ L1 xx = Link Lost Counter
Number of connection failures (hexadecimal) at X201 (OUT port)
*** Data error – error counter
§ R0 xx = Rx Error Counter
Number of data errors (hexadecimal) at X200 (IN port)
§ R1 xx = Link Lost Counter
Number of data fields (hexadecimal) at X201 (OUT port)
8.4.4 A259 | EtherCAT SM-Watchdog | V1
State of the SyncManager watchdog of the drive controller in the EtherCAT network (prerequisite: A258 = 65534).
§ [0]: Tolerated failure time (unit: ms)
Specified by the SyncManager watchdog function of the EtherCAT master
§ [1]: State
0 = not triggered; 1 = triggered = Event 52: Communication, cause 6: EtherCAT PDO-Timeout
§ [2]: Number of times triggered
8.4.5 A261 | Sync-Diagnostics | V1
Diagnostics of the synchronization of the drive controller in the EtherCAT network.
§ [0]: Error code
• 0 = No error
• 1 = SyncManager 2 and 3 have different cycle times
• 2 = Cycle time < 1ms
• 3 = Odd multiple of 1ms
• 4 = PLL could not be started
• 6 = Drive controller interrupt not initialized, firmware error
§ [1]: Time difference between the data provision and the Sync 0 signal
§ [2]: Error counter

Table of Contents

Other manuals for Stober SC6 Series

Related product manuals