© STULZ GmbH, Hamburg DE / 06-2016 / 1000687
-
99
-
STULZ UltraSonic -System for duct humidication ENS 14 A - 18 A- Maintenance Checklist
16. Maintenance Checklist
Procedure and maintenance interval
- Tightness of connections of water-bearing parts
- Cleanness of filter
- Outside of unit for impurities
-
Water tank for impurities, damage, microbial growth and
corrosion
-
Humidity sensor and ventilation slots for impurities
- Solenoid valves for deposits
Every 3 months**
☐
☐
☐
☐
☐
☐
☐
☐
☐
☐
☐
☐
☐
☐
☐
- Check oscillators for deposits
- Check mist guide pipes for deposits
☐
☐
☐
Inspect all screw and push-in connections for leaks and a secure fit
Remove housing cover and retaining plate together with mist
guide pipes (open water tank), clean and
disinfect with hydrogen peroxide solution
☐
☐
☐
☐
☐
☐
Remove cover of control system and check electrics
Open water tank, remove float switch and fill valve unit
Approx. every 10,000 operating hours**
Remove water tank, disconnect cables, detach oscillators
Approx. every 10,000 operating hours**
*
**
Time intervals may be shorter in isolated cases, depending on local conditions