DE / 06-2016 / 1000687 © STULZ GmbH, Hamburg
-
34
-
Installation STULZ UltraSonic -System for duct humidication ENS 14 A - 18 A-
CAUTION
Installation in an elevated location.
If installing the humidier in an elevated location, make sure that it is easily accessible for adjustments,
inspections, maintenance and repair work. Insufcient space can cause maintenance personnel to
suffer injuries and accidents!
CAUTION
Bear local conditions in mind.
Adapt the (on-site) fastening of the unit in line with local conditions.
CAUTION
Horizontal position.
The unit must be mounted precisely horizontally.
●
It is essential to check the position of the humidier before starting it up!
IMPORTANT
CAUTION
Adhere to set clearances.
Between the mist guide tube and any component that may be located in front of the unit, leave a clear-
ance that is greater than the humidier distance.
●
See section "5.1. Humidier distance" on page 27.
IMPORTANT
CAUTION
Direct exposure to air from air conditioning units.
Avoid directly exposing the humidier outlet to air from air conditioning units.
IMPORTANT
7.3. In-duct installation
Select the right type of installation to suit local circumstances. The examples below show the installation
of an ENS ultrasonic humidier on a bracket and in a duct. If the ultrasonic humidier is mounted on a
bracket, the safety overow must be connected to the drain via a hose. If it is not possible to connect the
safety overow to the drain, the ultrasonic humidier can be installed in a tray in which a water sensor is
tted.
Install the unit such that the expelled mist is distributed uniformly and everywhere in the duct (also see
section "5. Design and planning" on page 24). In order to achieve the shortest possible humidication
distances, it is important that the mist is distributed over the entire cross-section of the duct or unit as uni-
formly as possible, and that the air speed is kept in the range of 1.5 to 3 m/s. If this air speed is exceed-
ed, a perforated plate must be afxed in front of the air inlet of the humidier. Perforated plates reduce
the free diameter by more than 60%, and therefore effectively lower the air speed through the humidier.
Both perforated plates and the bracket are available from STULZ as optional accessories (see section
"3.1. Optional accessories" on page 11).
CAUTION
Maximum +40°C at humidier housing.
During the heating process, the air at the humidier housing must not exceed +40°C!