Installation STULZ UltraSonic -System for duct humidication ENS 14 A - 18 A-
7.4.2. Waste water connection
Ultrasonic humidiers from the ENS model series have two waste water connections.
CAUTION
Pressureless drainage.
The humidier drains without pressure.
●
Make sure the outlet allows free drainage.
Note
CAUTION
Flush valve.
Only install the ush valve in the DRAINAGE PIPE!
Note
CAUTION
Contaminated water pipes.
Filings and dirt must not get into water pipes!
●
All pipes must be cleaned before they are connected to the unit.
IMPORTANT
CAUTION
Position of valves.
Always install valves below the unit.
IMPORTANT
CAUTION
Direction of ow of solenoid valve.
Pay attention to the direction of ow when tting the solenoid valve.
IMPORTANT
CAUTION
Resistant materials.
The connection between the demineralization system and the humidier must consist of a material that
is resistant to demineralized water.
●
Only use approved materials. See "4.7. Application limits" on page 20.
IMPORTANT
CAUTION
Regulations from water supply companies.
Regulations from water supply companies must be complied with.
WARNING