STULZ UltraSonic -System for duct humidication ENS 14 A - 18 A- Troubleshooting
15. Troubleshooting
Troubleshooting table ENS 14 A - 18 A
Situation Cause Solution Explanation
No mist
production
A1 Unit is not in
operation
Start up the unit; check function of control
system
If the upstream control system is not functioning,
neither can the unit function.
A2 No supply voltage Check electrical supply, ensure power is
supplied to the unit
If the electrical supply between the humidier and
the control system is interrupted, the unit will not
function.
A3 Not enabled Enabling by control system, or ush func-
tion active, setpoint was reached; check
control system parameters and reset if
necessary
If the control system does not enable the unit or
the unit is in "Flush mode", no mist is produced.
A4 No clean water
supply
Check drinking water supply (all taps
open, on-site lters clogged, etc.), ensure
a supply of water, check ll valve
The low water oat switch FS2 was triggered by a
low water level, and has stopped the unit.
A5 Water level too
low
Check drinking water supply and upstream
water treatment system, ensure a supply,
check ll valve, check drain
If the ll valve does not open or the drain is contin-
uously open, a sufciently high water level can no
longer be reached, the low water oat switch FS2
stops the unit
A6 Safety chain
triggered
Check oat switches FS1 and FS2, check
voltage to motherboard (CH) slot CN1
contact 1/2 and slot CN2 contact 5
If a oat switch does not switch correctly or the
thermostat or water warning system has switched,
the unit stops the oscillators.
A7 Water does not
drain freely
Check water drain and repair if necessary The water supply oat switch FS1 was triggered
by a high water level, and closes the ll valve.
Water may escape from the overow.
A8 Faulty atomizer
unit
Check electrical supply H1/G1 and H2/G2 If the oscillators do not function despite the power
being on, they are faulty.
Low mist
production
B1 Supply voltage
too low
Check transformer If the transformer does not generate 48V AC
(+/- 10%), the supply voltage is too low for normal
operation.
B2 Unit is incorrectly
installed
Check that the unit is installed as
described in the "Humidier distance"
section
If the unit is not horizontal, or if the mist cannot be
correctly distributed in the room due to incorrect
mounting, this will affect mist production.
B3 Worn atomizers Check operating hours, visually inspect
oscillators
The capacity of the oscillators declines if they are
dirty or have reached the end of their life.
B4 Request by con-
trol system
Check setpoints and actual values If the setpoint given by the control system is
approximately reached, depending on the control
system the oscillators may only be requested to
act briey.
B5 Inadequate
airow
Check installation, fan and air lter If the airow volume is too low due to a faulty fan,
a clogged lter or an incorrectly installed unit, this
directly affects mist production.
B6 Intake pressure
of demineralized
drinking water
too low
Check drinking water supply and upstream
water treatment system and ensure a sup-
ply if necessary; optimize supply channels
If the intake pressure at the humidier is insuf-
cient, the ll valve cannot be guaranteed to open
reliably.
Water escapes
from the
overow
C1 "Upper water
level" oat switch
is not triggered
Check correct seating and function of oat
switch
The water supply oat switch FS1 should close
the supply valve when the maximum water level is
reached.
C2 Supply valve
does not close
Check function of supply valve If the valve is open (e.g. clogging, mechanical
fault), water is fed to the humidier continuously.
C3 Drain is
obstructed
Check drain and drainage valve If the drain is blocked, the ush valve is closed
or the unit is not correctly installed, water may
escape from the overow