4 Mechanical Mounting User Manual
16
4.2.1 Installation Environment Requirements
The installation environment is free of inflammable or explosive materials.
The inverter should be installed in a place inaccessible to the children.
The ambient temperature and relative humidity should meet the following
requirements.
Max.+60°C
Min. -30°C
Max. RH: 100%
(non-condensing)
The inverter should be protected against exposure to direct sunlight, rain, or
snow to ensure longer service life.
The inverter should be well ventilated. Ensure air circulation.
Never install the inverter in living areas. The inverter will generate noise
during operation, affecting daily life.
4.2.2 Carrier Requirements
The installation carrier should meet the following requirements:
Made of non-inflammable materials
Max. load bearing capacity 4
times of inverter weight
KG
4.2.3 Installation Angle Requirements
Inverter vertically or at a minimum back tilt of 10°. Forward installation or upside
down installation is prohibited.
DC SWITCH
ON
OFF
DC SWITCH
ON
OFF
Forward
Backward
DC SWITCH
ON
OFF
DC SWITCH
ON
OFF
10°
Upside down
DC SWITCH
ON
OFF
DC SWITCH
ON
OFF
DC SWITCH
ON
OFF
DC SWITCH
ON
OFF
Vertical