9 Troubleshooting and Maintenance User Manual
78
Risk of inverter damage if it is improperly serviced.
Use accessories and spare parts approved by the inverter manufacturer
only. Never modify the inverter or other components of the inverter.
Unauthorized alterations will void guarantee and warranty claims and in
most cases terminate the operating license. SUNGROW shall not be held
liable for any damage caused by such changes.
Any malfunction that may impair the inverter safety operation must be
repaired immediately before the inverter is restarted.
Inverter contains no customer serviceable parts inside. Please contact local
authorized personnel if any service work is required.
9.2.1 Routine Maintenance
Item
Method
Period
System
clean
Check the temperature and dust of the
inverter. Clean the inverter enclosure if
necessary.
Check if the air inlet and outlet are
normal. Clean the air inlet and outlet, if
necessary.
Six months to a year
(depend on the dust
contents in air.)
Fans
Check whether there is fan warning
using APP.
Check whether there is any abnormal
noise when the fan is turning.
Clean or replace the fans if necessary
(see the following section).
Once a year
Cable entry
Check whether the cable entry is
insufficiently sealed or the gap is
excessively large, and reseal the entry
when necessary.
Once a year
Electrical
Connection
Check whether all cable are firmly in
place.
Check whether a cable is damaged,
especially the part contacting the metal
enclosure.
Six months to a year
9.2.2 Maintenance Instruction
Fan Maintenance
Fans inside the inverter are used to cool the inverter during operation. If the
fans do not operate normally, the inverter may not be cooled down and inverter

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Sungrow SG33CX and is the answer not in the manual?

Sungrow SG33CX Specifications

General IconGeneral
ModelSG33CX
ManufacturerSungrow
Rated Power33 kW
Max DC Voltage1100 V
Max Efficiency98.7%
Start Voltage200 V
Total Harmonic Distortion< 3%
Power Factor at Rated Power1
DC Connection TypeMC4
Allowable Relative Humidity Range0 - 100%
Operating Altitude4000 m
MPPT Voltage Range200 V - 1000 V
AC Voltage Range310 V - 480 V
Rated Grid Frequency50 Hz / 60 Hz
Adjustable Power Factor Range0.8 leading to 0.8 lagging
Operating Ambient Temperature Range-25 °C ... +60 °C
CommunicationRS485