EasyManuals Logo

Sungrow SG33CX User Manual

Sungrow SG33CX
95 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #92 background imageLoading...
Page #92 background image
10 Appendix User Manual
82
Parameters
SG33CX
SG40CX
SG50CX
Nominal AC voltage
3 / N / PE230 / 400V
AC voltage range
312~528V
Nominal grid
frequency/Grid
frequency range
50Hz / 45~55Hz60Hz / 55~65Hz
Total harmonic distortion
(THD)
< 3 % (at nominal power)
DC current injection
<0.5%In
Power factor
>0.99
Adjustable power factor
0.8 leading 0.8 lagging
Feed-in phases /
Connection phases
3/3
Efficiency
Max. efficiency /
European efficiency
98.6% / 98.3%
98.6% / 98.3%
98.7% / 98.4%
Protection
DC reverse connection
protection
Yes
AC short-circuit
protection
Yes
Leakage current
protection
Yes
Grid monitoring
Yes
DC switch / AC switch
Yes / No
PV string current
monitoring
Yes
Q at night
Yes
PID recovery function
Optional
Overvoltage protection
DC Type II / AC Type II
General Data
Dimensions (W*H*D)
702 × 595 ×
310mm
782 × 645 ×
310mm
782 × 645 ×
310mm
Weight
50kg
58kg
62kg
Isolation method
Transformerless
Degree of protection
IP66
Night power
consumption
2 W
Operating ambient
temperature range
-30 to 60 (> 45 derating)
Allowable relative
humidity range
(non-condensing)
0 - 100%
Cooling method
Smart forced air cooling
Max. operating altitude
4000 m (> 3000 m derating)
Display
LED, Bluetooth + APP
Communication
RS485/ Wi-Fi(optional)/Ethernet(optional)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Sungrow SG33CX and is the answer not in the manual?

Sungrow SG33CX Specifications

General IconGeneral
ModelSG33CX
ManufacturerSungrow
Rated Power33 kW
Max DC Voltage1100 V
Max Efficiency98.7%
Start Voltage200 V
Total Harmonic Distortion< 3%
Power Factor at Rated Power1
DC Connection TypeMC4
Allowable Relative Humidity Range0 - 100%
Operating Altitude4000 m
MPPT Voltage Range200 V - 1000 V
AC Voltage Range310 V - 480 V
Rated Grid Frequency50 Hz / 60 Hz
Adjustable Power Factor Range0.8 leading to 0.8 lagging
Operating Ambient Temperature Range-25 °C ... +60 °C