User Manual 8 Troubleshooting and Maintenance
57
021 PV1 input over-current.
Check the layout and the wiring of PV1
input.
022 PV2 input over-current.
Check the layout and the wiring of PV2
input.
Check the cable connections of PV1.
029
Check the cable connections of PV2.
036
The temperature of
radiator is too high.
1. Check whether the ambient temperature
shown on the screen is too high. Wait a
moment for inverter recovery.
2. Check whether there is enough space for
convection.
3. Check whether the inverter is in direct
sunlight.
4. Check whether the fan is normal.
Replace it if necessary.
5. Clean the air inlets.
6. If the fault persists, please contact
Sungrow.
temperature of inverter
is too high.
038
Relay fault on the grid
side.
1. Wait a moment for inverter recovery.
2. If the fault occurs repeatedly, contact
1. Check whether there is a reliable inverter
grounding line.
2. Check whether one of the PV strings is
short-circuited with ground.
3. Wait a moment for inverter recovery.
4. If the fault occurs repeatedly, contact
1. Wait a moment for inverter recovery.
2. If the fault occurs repeatedly, contact
The inverter will recover once the ambient
temperature rises above -25℃.
Inverter self-test fault.
1. Wait a moment for inverter recovery.
2. If the fault occurs repeatedly, contact
Sungrow Service Dept.
045
Phase current
sampling fault.