8 Troubleshooting and Maintenance User Manual
58
053
The slave DSP detects
that the
exceeds inverter
allowable upper limit.
1. Check the grid voltage.
2. If the grid voltage exceeds the
permissible range of inverter protection
parameters, ask utility grid company for
3. If the grid voltage is within the
permissible range, contact Sungrow Service
054
The slave DSP detects
that the grid frequency
exceeds inverter
allowable upper limit.
1. Check the grid frequency.
2. If the grid frequency exceeds the
permissible range of inverter protection
ask utility grid company for
3. If the grid frequency is within the
permissible range, contact Sungrow Service
current exceeds
inverter allowable
upper limit.
1. Check whether there is a grounded fault
of the PV string.
2. If the fault occurs repeatedly, contact
Sungrow Service Dept.
059
Communication alarm
between master DSP
and slave DSP.
1. Wait 1 minute for inverter recovery.
2. If the fault persists, contact Sungrow
Alarm for no inverter
type setting.
Contact Sungrow Service Dept.
070 Fans are defective
Stop the inverter and disconnect the AC &
DC cables. Check whether the fan duct has
been blocked. If not, replace fans.
cable connection of the
Sungrow Meter.
1. Check whether the power cable
connections are correct.
2. If “Existing Inverter” is set to “ON” via
LCD menu, check and ensure that its rated
power is correctly set.
3. For Sungrow single-phase meter, check
whether the CT clamp of the 1-phase
sensor is correctly placed. Refer to “5.6.1
Mismatched software
version.
Please contact Sungrow Service Dept.
100
The AC output current
exceeds the upper
limit.
1. The inverter will resume if the output
current falls below the protection value.
2. If the fault
persists, please contact
Sungrow Service Dept.