User Manual 8 Troubleshooting and Maintenance
59
Grid over-frequency.
The grid frequency
exceeds the protective
value, which is higher
1. Check the grid frequency.
2. If the grid frequency exceeds the
ermissible range of inverter protection
parameters, ask utility grid company for
3. If the grid frequency is within the
permissible range, contact Sungrow Service
Dept.
102
The grid frequency is
below
which is lower
than the protective
Neither the PE terminal
on the AC connection
block nor the second
PE terminal on the
enclosure is reliably
connected.
Check whether there is a reliable inverter
grounding line, if there is access to the
ground, and the fault persists, please
contact Sungrow Service Dept.
200
1. Wait for inverter recovery after bus
voltage lower.
2. If the fault occurs repeatedly, contact
Sungrow Service Dept.
201
The bus voltage is too
low.
1. Wait a moment for inverter recovery.
2. If the fault occurs repeatedly, contact
If the fault occurs repeatedly, contact
Sungrow Service Dept.
203
Check the functionality of the PV
connection terminals.
306
Input and output power
mismatching fault.
If the fault occurs repeatedly, contact
Sungrow Service Dept.
PV1 current sampling
fault.
Channel sampling anomaly.
Contact Sungrow Service Dept.
316
PV2 current sampling
fault.
Leakage current
sensor fault.
Contact Sungrow Service Dept.
409
All temperature
sensors fail.
If the fault occurs repeatedly, contact
Sungrow Service Dept.