SINGLE PHASE HI 8kW | User Manual71
5.20. Advanced Settings for Wind Turbines
To congure wind turbine settings, click on the ADVANCE icon.
What this page displays:
If one or both of the MPPTs are connected to a wind turbine.
What you can do from this page:
Select the MPPT to be used as a turbine input.
The table below shows the maximum current depending on the voltage of the wind turbine.
PLEASE NOTE
DO NOT use a wind turbine that exceeds 400V.
Use a self-breaking wind turbine. Once the batteries are fully charged and the inverter is not ex-
porting any power, the load can drop. This can cause the turbine to speed up dramatically, which
can be very dangerous and usually happens suddenly. Thus, it is essential to use a self-breaking
turbine.
Voltage (V) Max. Current (A) Power (W)
150 23.33 3500
200 17.50 3500
250 14.00 3500
300 11.67 3500
400 8.75 3500