Sutron Corporation Satlink Operations & Maintenance Manual, Rev 8.04.2 11/3/2016 pg. 28
The key settings for mv output sensors are:
Measurement Type: Analog
Analog type: Diff C, D or E
Input Range: 39mV, 312mV, 2.5V, 39mV w/Bias, 312mv w/Bias.
Note: use the range with Bias for any sensor (such as a pyranometer) that does not
connect to VREF or other SL3 power
4.17. Connecting Thermistors
Thermistors connect to SL3 to the A or B channels as shown below. Note there is a precision 10K
reference resistor between the input and +2.5VREF.
The key settings for thermistors are:
Measurement Type: Analog
Analog type: A or B
Equation to compute temperature (Celsius):