Alarm no.
Alarm text
Function
Priority Stop Indication
LED
Delay Resetting
0=blocked 0=In operat. 0=Off s=seconds M=manual
A=A alarm 1=Stop 1=On m=minutes A=automatic
B=B alarm
105
HEAT. CIRCUIT PUMP I/O-7 TRIPPED
Controls of the heating circuit pump do not obtain
correct signal according to set function.
A*** 1 1 30 s M
106
COOLING WATER TEMP I/O-7 BELOW SET POINT
Temperature for cooling water control on I/O module
is continuously 7°C below its current set point.
B*** 1 1 30 m M
107
HEATING WATER TEMP I/O-7 BELOW SET POINT.
Temperature for heating water control on I/O module
is continuously 7°C below its current set point.
A*** 1 1 30 m M
108
COOLING WATER TEMP I/O-7 ABOVE SET POINT
Temperature for cooling water control on I/O module
is continuously 7°C above its current set point.
0*** 1 1 30 m M
109
HEATING WATER TEMP I/O-7 ABOVE SET POINT
Temperature for heating water control on I/O module
is continuously 7°C above its current set point.
0*** 1 1 30 m M
110
COOLING WATER TEMP SENSOR I/O-7 DEFECTIVE
Obtained if the cooling water temperature sensor
temp is not connected or is defective.
B 1 1 3 s A
111
HEATING WATER TEMP SENSOR I/O-7 DEFECTIVE
Obtained if the heating water temperature sensor is
not connected or is defective.
A 1 1 3 s A
112-
134
SPARE
135
SA FAN MOTOR BLOCKED
Motor shaft does not rotate during start up.
A*** 1 1 3 sec. M
136
EA FAN MOTOR BLOCKED
Motor shaft does not rotate during start up.
A*** 1 1 3 sec. M
137
SA-2 FAN MOTOR BLOCKED
Motor shaft does not rotate during start up.
A*** 1 1 3 sec. M
138
EA-2 FAN MOTOR BLOCKED
Motor shaft does not rotate during start up.
A*** 1 1 3 sec. M
139
FLUCTUATION VOLTAGE BETWEEN THE PHASES, SA
High voltage difference between the phases
(3-phase, 400 V), which causes rippling.
A*** 1 1 3 sec. M
140
FLUCTUATION VOLTAGE BETWEEN THE PHASES, EA
High voltage difference between the phases
(3-phase, 400 V), which causes rippling.
A*** 1 1 3 sec. M
141
FLUCTUATION VOLTAGE BETWEEN THE PHASES,
SA-2
High voltage difference between the phases
(3-phase, 400 V), which causes rippling.
A*** 1 1 3 sec. M
142
FLUCTUATION VOLTAGE BETWEEN THE PHASES,
EA-2
High voltage difference between the phases
(3-phase, 400 V), which causes rippling.
A*** 1 1 3 sec. M