GB.GOLDSK509.091101
We reserve the right to alter specifications without notice.
www.swegon.com 69
Function Factory preset value Adjusted value
Outdoor temp. compensation Inactive
Flow
Winter comp. Y1 (%) 30
End point, winter X1 (°C) -20
Start point winter X2 (°C) 10
Boosting
SA
X Inactive Active Inactive Active
EA
X Inactive Active Inactive Active
Down-regulation
8)
Function
Inact. X SA SA+EA Inact. SA SA+EA
Neutral zone (°C) 0.0
Operation
Switch clock function X 1. Low - High 2. Stop - Low - High 1. Low - High 2. Stop - Low - High
Slave control
9)
Cooling COP 1.0
Filter function GOLD SD
X Inact. SA EA SA+EA Inact. SA EA SA+EA
Prefilter
X Inact. SA EA SA+EA Inact. SA EA SA+EA
Prolonged operation
Ext. low speed (h:mm) 0:00
Ext. high speed (h:mm) 0:00
Summer/wintertime
Inactive X Active Inactive Active
Heating
Heat exchanger GOLD RX
Defrosting
X Inactive Active Inactive Active
Exhaust air regulation
Function
X Inact. Active Inact. Active
Min. temp (°C) 5
Re-heating
8)
Pumpexercizing Inact. X Pump Valve P+V Inact. Pump Valve P+V
Exercizing period 3 Min.
Interval 24 h
"Heating boost"
8)
Function Off/On
X Inactive Auto op. Inactive Auto op.
Start limit SA Temp. (°C) 3.0