Function Factory preset value Adjusted value
8)
Exercising Cooling relay 1
X Inact. Pump Valve P+V Inact. Pump Valve P+V
Cooling relay 2
X Inact. Pump Valve P+V Inact. Pump Valve P+V
Exercise period 3 min.
Interval 24 hrs.
Response speed
Step period (s) 300
Outd. temp limit Step 1 (°C) 3.0
Step 2 (°C) 5.0
Step 3 (°C) 7.0
Reset period (s) 480 (CoolDX: 300)
Cool. - min SA flow (m³s)
6)
Cool. - min EA flow (m³s)
6)
Neutral zone (°C) 2.0
"Cooling Boost"
8)
X Inact. Comf. Econ. Sequ. Inact. Comf. Econ. Sequ.
Comf.+Econ. Econ.+Sequ. Comf.+Econ. Econ.+Sequ.
Start limit SA temp (°C) 3.0
Hunidity
8)
Dehumidification control
X Inactive Active Inactive Active
Rel. hum., SA (%RH 50%
Steppless
0-10 V
Steppless
10-0 V
CoolDX
Comfort
On/off
1 step
On/off
2 steps
Inactive Active
Cooling
Refr. Machine control
Steppless
0-10 V
Steppless
10-0 V
CoolDX
Comfort
On/off
1 step
On/off
2 steps
Inactive Active
X
X
CoolDX
Economy
CoolDX
Economy
On/off
3 steps binary
On/off
3 steps binary
COOL DXS COOL DXS