Function Factory preset value Adjusted value
All Year Comfort 8) X Inact. Cool. Heat. C+H Inact. Cool. Heat. C+H
Heating water temp. (°C) 30
Cooling water temp. (°C) 14
Outdoor comp., Heating water
X Inact. Active Inact. Active
Outdoor temp. (X1) (°C) -20
Heating water (Y1)(°C) 40
Outdoor temp. (X2)(°C) 5
Heating water (Y2)(°C) 30
Outdoor temp. (X3)(°C) 15
Heating water (Y3)(°C) 20
Outdoor comp., Cooling water
X Inact. Active Inact. Active
Outdoor temp. (X1) (°C) 10
Cooling water (Y1)(°C) 22
Outdoor temp. (X2)(°C) 20
Cooling water (Y2)(°C) 18
Outdoor temp. (X3)(°C) 25
Cooling water (Y3)(°C) 14
Room comp., Heating water
X Inact. Active Inact. Active
Room temperature (°C) 21
P-band (°C) 5
Night blocking
Inact. Active Inact. Active
Room comp., Cooling water
X Inact. Active Inact. Active
Room temperature (°C) 21
P-band (°C) 5
Night blocking
Inact. Active Inact. Active
Night comp., Heating water
X Inact. Active Inact. Active
Temp. comp. (°C) -2
Night comp., Cooling water
X Inact. Active Inact. Active
Temp. comp. (°C) 2
Night comp.
X Inact. Active Inact. Active
Channel 1, Start, Stop, Weekday Inactive
Channel 2, Start, Stop, Weekday Inactive
Pump operation, Heating water
Outdoor temp. Start (°C) 15
Outdoor temp. Stop (°C) 18
Pump operation, Cooling water
Outdoor temp. Start (°C) -20
Outdoor temp. Stop (°C) -25
Alarm function, Heating water
Pump alarm X Inact. Open Close Cont. Inact. Open Close Cont.
Valve
X Inact. Active Inact. Active
Alarm function, Cooling water
Pump alarm X Inact. Open Close Cont. Inact. Open Close Cont.
Valve
X Inact. Active Inact. Active
Exercising, Heating water X Inact. Pump P+V Valve Inact. Pump P+V Valve
Exercising period, (min) 3
Interval (h) 24
Exercising, Cooling water X Inact. Pump P+V Valvev Inact. Pump P+V Valve
Exercising period, (min) 3
Interval (h) 24
Dew point comp.
X Inact. Active Inact. Active
Neutral zone (°C) 2
Comp. air flow (%) 10