GB.GOLDSK509.091101
We reserve the right to alter speciļ¬cations without notice.
72
www.swegon.com
Function Factory preset value Adjusted value
CONTROL Optimize 8)
X Inactive Active Inactive Active
Upper damper limit (%) 90
Lower damper limit (%) 70
Step size (Pa) 20
Interval (min) 2
Permissible deviation (Pa) 10
Power up start delay (min) 15
Min. pressure (Pa) 50
Max. pressure (Pa) 400
"IQnomic Plus"
I/O module Nr 0 ReCO2
X Inactive Active Inactive Active
I/O module Nr 1 Coil heat exch.
X Inactive Active Inactive Active
I/O module Nr 2 Plate heat exch.
X Inactive Active Inactive Active
I/O module Nr 3 Ext. monitoring
X Inactive Active Inactive Active
If active, function:
I/O module Nr 6
8) Ext. cooling
X Inactive Active Inactive Active
I/O module Nr 7 All Year Comfort
X Inactive Active Inactive Active
I/O module Nr 8 8) Swegon Factory
X Inactive Active Inactive Active
I/O module Nr 9 Preheating
X Inactive Active Inactive Active
I/O module Nr A Heating zone
X Inactive Active Inactive Active
I/O module Nr B
Cooling zone
X Inactive Active Inactive Active