GB.GOLDSK509.091101
We reserve the right to alter specifications without notice.
www.swegon.com 73
Function Factory preset value Adjusted value
ReCO
2
CO
2
function
X Inact. CO
2
Co
2
+flow
Inact. CO
2
Co
2
+flow
Temperature function Cooling
X Inact. Comf. Econ.
Inact. Comf. Econ.
Temperature function Heating
X Inact. Comf. Econ.
Inact. Comf. Econ.
Min. outdoor air
6)
Min. exhaust air
6)
Alarm setting
Fire alarm function
Internal fire alarms
X Inactive Active Inactive Active
External fire alarms Alarm Reset
X Man. Auto Man. Auto
Fans in event of fire
X Inact. SA EA SA+EA Inact. SA EA SA+EA
SA fan speed in event of fire (%) 100
EA fan speed in event of fire (%) 100
External alarm
Time delay - alarm 1 (s) 10
Alarm on closure, alarm 1 1
Alarm Reset
X Man. Auto Man. Auto
Time delay- alarm 2 (s) 10
Alarm on closure, alarm 2 1
Alarm Reset
X Man. Auto Man. Auto
Alarm limit temp.
8)
Deviation - SA setpoint 5.0
Min EA temperature 15.0
Filter alarm limit
SA (Pa) 100
EA (Pa) 100
Heat exch. defrosting
Alarm limit (Pa) GOLD RX 50