4-123
Output is active when the output frequency falls within the frequency detection width
(03-14) of the set frequency detection level (o3-13)
(4) Setting Frequency Agree (03-13 ± 03-14) (03-1X=3)
Output is active when the output frequency falls within the frequency detection width
(03-14) of the set frequency detection level (o3-13).
(5) Frequency Detection 1 (≧ 03-13, hysteresis range is the value of 03-14) (03-1X=4)
Output is active when the output frequency rises above the frequency detection level (03-13) +
frequency detection width (o3-14) and deactivates when the output frequency falls below
frequency detection level (o3-13).
(6) Frequency Detection 2 (≦ 03-13, hysteresis range is the value of 03-14) (03-1X=5)
Output is active when the output frequency is below the frequency detection level
(03-13) + frequency detection width (03-14) and turns off when the output frequency
falls below frequency detection level.
(7) Automatic restart (03-1X=6)
Output is active during an auto-restart operation.
(8) Momentary AC Power Loss (03-1X=7)
Output is active during momentary AC power loss.
(9) Rapid Stop (03-1X=8)
Output is active during a rapid stop.
(10) Base Block (03-1X=9)
Output is active when the inverter output is turned off during a Baseblock command.
(11) Motor Overload Protection (OL1) (03-1X=10)
Output is active during an overload detection of motor.
(12) Drive Overload Protection (OL2) (03-1X=11)
Output is active during an overload detection of inverter.
(13) Over Torque Threshold Level (OL3) (03-1X=12)
Output is active during an over torque detection of inverter.
(14) Preset Output Current Reached (03-1X=13)
When output current > 03-15 and output current > 03-15 duration > 03-16, it is ON.
(15) Brake Control (03-1X=14)
Output is active when the brake control is active.