4-124
(16) PID Feedback Signal Loss (03-1X=15)
Output is active when PID feedback signal loss.
(17) PLC Status Indicator (03-1X=18)
Output is active when operation command parameter 00-02 is set to PLC control.
(18) PLC Control (03-1X=19)
Output is controlled by the PLC logic.
(19) Zero Speed (03-1X=20)
When zero speed is active, output frequency < minimum output frequency (01-08).
When zero speed is off, output frequency ≧ minimum output frequency.
ONOFF
01-08 (Fmin)
Output
Frequency
Zero Speed
t
t
Figure 4.3.26 Zero speed operation
(20) Motor 2 Selection (03-1X=30)
Output is active when motor 2 is selected.
(21) Detection Output of PID Feedback Loss (03-1X=37)
Output is active when PID feedback loss.
(22) Turn On Short Circuit Braking (03-1X=54)
Output is active when truning on short circuit braking.
(23) Low Current Detection (03-1X=55)
Output is active when low current detection function is active.
(24) OH Detection (03-1X=59)
Output is active when temperature setting is agreed.
03-13 Frequency detection Level
Range
【0.0~599.0】 Hz
03-14 Frequency detection width
Range 【0.1~25.5】 Hz
Frequency detection level:the multi-function output terminals R1A-R1C, R2A-R2C or PH1
(03-11, 03-12) to the desired detection level and bandwidth for use with multi-function output