4-125
functions 1 to 6.
The time charts of the frequency agree detection operation are shown in table 4.3.30.
Function
Detection operation of frequency
confirmation
Description
Frequency
agree
time
time
ONOFF
FWD
REV
03-14
03-14
Freq
Reference
Output
Frequency
Frequency
Agree
Signal
ON
Freq
Reference
Output is active when the output
frequency falls within the frequency
reference minus the frequency
detection width (03-14).
Any of the digital outputs function
(03-11, 03-12 or 03-28) can be set to 2
(Frequency agree).
Set
frequency
agree
time
time
ONOFF
FWD
REV
03-14
Output
Frequency
Setting
Frequency
Agree
Signal
ON
03-13
03-13
03-14
Output is active the output frequency
falls within the frequency detection
width (03-14) of the set frequency
detection level (03-13).
Any of the digital outputs function
(03-11, 03-12 or 03-28) can be set to 3
(Set frequency agree).
Output
frequency
detection
1
ON ONOFF OFF
03-14
03-14
03-13
03-13
03-13
03-13
tim
e
tim
e
Output
Frequency
Output
Frequency
Detection 1
Signal
Output is active when the output
frequency rises above the frequency
detection level (03-13) + frequency
detection width (o3-14) and
deactivates when the output
frequency falls below frequency
detection level (03-13).
Any of the digital outputs function
(03-11, 03-12 or 03-28) can be set to 4
(Output frequency detection 1).
Output
frequency
detection
2
Output is active when the output
frequency is below the frequency
detection level (03-13) + frequency
detection width (03-14) and turns off
when the output frequency rises above
below frequency detection level.
Any of the digital outputs function
(03-11, 03-12 or 03-28) can be set to 5
(Output frequency detection 2).
Frequency
Output
DC BrakeDC Brake
ON ONOFF OFF
Output
Frequency
Frequency
Output
Ing
OFF
OFF
OFF
OFF OFF
ON
ON
Run
command
Base
Block
When the inverter output frequency is
active, the output terminal is closed.