4-126
Function
Detection operation of frequency
confirmation
Description
03-15 Current Agree Level
Range 【0.1~999.9】A
03-16 Delay Time of Current Agree Detection
Range 【0.1~10.0】 Sec
When 03-11=13 and then when the output current > 03-15, output relay will active.
03-15:The suggest setting value is 0.1 to motor rated current.
03-16:The delay time performs depending one the setting value.
When output current lower than 03-53, delay time from ON to OFF in the signal of relay is
100ms (constant).
Time diagram:
03-17 Machanical Braking Release Level
Range 【0.00~20.00】 Hz
03-18 Machanical Braking Level Set
Range 【0.00~20.00】 Hz
When 03-11=14,
In acceleration mode, output relay will be ON as soon as the actual output frequency
reaches the external brake release set in parameter 03-17.
In deceleration mode, output relay will be OFF as soon as the actual output frequency
reachesthe external brake engage level set in parameter 03-18.
Timing diagram for 03-17 ≤ 03-18 is shown below.