CHAPTER 5– CONNECTING FIELD DEVICES TO THE I/O BOARD
44 MultiLoad II/ RCU II Explosion Proof Lite (EXL) Installation Guide - Part # 6070
5.4.4.2 MultiLoad II 4 – 20 mA Input Wiring
* Note: The 4-20 mA receiver does not contain a voltage source. The loop must be powered either by the transmitter or by an external power
supply. The I/O Board adds 75 Ohms to the loop.
† Note: “4-20 mA IN.I-” MUST CONNECT TO LOOP SUPPLY- !
‡ Note: A separate supply powers the transmitter. 4-20 mA IN.I+ must be connected to the transmitter’s current output.
DO NOT CONNECT “4-20 mA IN.I+” TO LOOP SUPPLY+ !