6. Connect common wire(s) first. To momentarily operate a valve 
for identification and/or functional test, touch it’s control wire 
to the 24 VAC Hot Post. When operation has been 
confirmed, connect the wire to the preferred station terminal.
Note: Each field wire connection block provides 12 station outputs 
(black) and one common output (green). The lower left connection 
block provides one master valve/pump start relay output (blue). 
To connect wire, push orange tab in, insert wire, then release. Pull 
lightly on wire to confirm retention. 
   Caution: The controller must not be connected directly to 
a pump or other high current-draw equipment. A 24 VAC, 0.5A 
(max.) relay must be used to facilitate the connection. Failure 
to comply can result in severe controller damage.
!