106 HX7+ ASD Installation and Operation Manual
RR Speed Frequency #1
Program Frequency Setting Speed Reference Setpoints RR
This parameter is used to set the gain and bias of the RR input terminal when
the RR terminal is used as the control input while operating in the Speed
Control mode.
See RR Speed Reference #1 (F210) for further information on this setting.
This parameter sets RR Speed Frequency #1 and is the frequency that is
associated with the setting of RR Speed Reference #1 while operating in the
Speed Control mode.
Direct Access Number — F211
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Ye s
Minimum — 0.0
Maximum — Max. Freq. (F011)
Units — Hz
RR Speed Reference #2
Program Frequency Setting Speed Reference Setpoints RR
This parameter is used to set the gain and bias of the RR input terminal when
the RR terminal is used as the control input while operating in the Speed
Control mode or the Torque Control mode.
See RR Speed Reference #1 for further information on this setting when used
for Speed control or Torque control.
This parameter sets the RR input level that is associated with RR Speed
Frequency #2 while operating in the Speed control mode or is associated with
the RR Torque Reference Setpoint #2 while operating in the Torque control
mode.
Direct Access Number — F212
Parameter Type — Numerical
Factory Default — 100.00
Changeable During Run — Ye s
Minimum — 0.0
Maximum — 100.0
Units — %
RR Speed Frequency #2
Program Frequency Setting Speed Reference Setpoints RR
This parameter is used to set the gain and bias of the RR input terminal when
the RR terminal is used as the control input while operating in the Speed
Control mode.
See RR Speed Reference #1 for further information on this setting when used
for Speed control.
This parameter sets RR Speed Frequency #2 and is the frequency that is
associated with the setting of RR Speed Reference #2 while operating in the
Speed Control mode.
Direct Access Number — F213
Parameter Type — Numerical
Factory Default — 80.00
Changeable During Run — Ye s
Minimum — 0.0
Maximum — Max. Freq. (F011)
Units — Hz
RR Torque Reference Setpoint #1
Program Torque Setting Setpoints RR
This parameter is used to set the gain and bias of the RR input terminal when
the RR terminal is used as the control input while operating in the Torque
Control mode.
This is accomplished by establishing an associated V/f output pattern for a
given RR input level.
See RR Speed Reference #1 for further information on this setting.
This parameter sets RR Torque Reference Setpoint #1 and is the output torque
value that is associated with the setting of RR Speed Reference #1 while
operating in the Torque control mode.
Direct Access Number — F214
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Ye s
Minimum — 0.00
Maximum — 250.0
Units — %
F211 F214