HX7+ ASD Installation and Operation Manual 109
RX Speed Frequency #1
Program Frequency Setting Speed Reference Setpoints RX
This parameter is used to set the gain and bias of the RX input terminal when
the RX terminal is used as the control input while operating in the Speed
Control mode.
See RX Speed Reference #1 (F216) for further information on this setting.
This parameter sets RX Speed Frequency #1 and is the frequency that is
associated with the setting of RX Speed Reference #1 while operating in the
Speed Control mode.
Direct Access Number — F217
Parameter Type — Numerical
Factory Default 0.0
Changeable During Run — Ye s
Minimum — -Max. Freq. (F011)
Maximum — Max. Freq. (F011)
Units — Hz
RX Speed Reference #2
Program Frequency Setting Speed Reference Setpoints RX
This parameter is used to set the gain and bias of the RX input terminal when
the RX terminal is used as the control input while operating in the Speed
Control mode or the Torque Control mode.
See RX Speed Reference #1 for further information on this setting when used
for Speed control or Torque control.
This parameter sets the RX input level that is associated with RX Speed
Frequency #2 while operating in the Speed control mode or is associated with
the RX Torque Reference Setpoint #2 while operating in the Torque control
mode.
Direct Access Number — F218
Parameter Type — Numerical
Factory Default 100.00
Changeable During Run — Ye s
Minimum — -100.0
Maximum — 100.0
Units — %
RX Speed Frequency #2
Program Frequency Setting Speed Reference Setpoints RX
This parameter is used to set the gain and bias of the RX input terminal when
the RX terminal is used as the control input while operating in the Speed
Control mode.
See RX Speed Reference #1 for further information on this setting when used
for Speed control.
This parameter sets RX Speed Frequency #2 and is the frequency that is
associated with the setting of RX Speed Reference #2 while operating in the
Speed Control mode.
Direct Access Number — F219
Parameter Type — Numerical
Factory Default 80.00
Changeable During Run — Ye s
Minimum — -Max. Freq. (F011)
Maximum — Max. Freq. (F011)
Units — Hz
RX Torque Reference Setpoint #1
Program Torque Setting Setpoints RX
This parameter is used to set the gain and bias of the RX input terminal when
the RX terminal is used as the control input while operating in the Torque
Control mode.
This is accomplished by establishing an associated V/f output pattern for a
given RX input level.
See RX Speed Reference #1 for further information on this setting.
This parameter sets RX Torque Reference Setpoint #1 and is the output torque
value that is associated with the setting of RX Speed Reference #1 while
operating in the Torque control mode.
Direct Access Number — F220
Parameter Type — Numerical
Factory Default 0.00
Changeable During Run — Ye s
Minimum — -250.00
Maximum — 250.00
Units — %
F217 F220