HX7+ ASD Installation and Operation Manual 191
86 87
Binary Data Write — This terminal serves two functions:
1) While operating in the Use Binary/BCD input mode, each momentary connection of this terminal to CC transfers
the speed/torque Binary Bit (0 – MSB) settings to the motor.
2) The Motorized Pot frequency command will be saved during power down or reset by setting F108 to Store and
activating this terminal (Binary Data Write). If the drive is running and the Binary Data Write terminal is active
when an event occurs (Fault, Power off), the Motorized Pot frequency command will be restored upon power-up or
reset.
88 89
Motorized Pot Up (MOP) — Activation initiates an increase in motor speed for the duration of the activation until
the Upper Limit is reached. The Frequency Mode setting must be set to Motorized Pot. Simulation. The MOP
acceleration rate is determined by the
F500 setting.
90 91
Motorized Pot Down (MOP) — Activation initiates a decrease in motor speed for the duration of the activation until
the Lower Limit is reached. The Frequency Mode setting must be set to Motorized Pot. Simulation. The MOP
deceleration rate is determined by the F501 setting.
92 93
Motorized Pot Clear — Activation clears the last Motorized Pot frequency settings (see F108 for further
information on this setting).
94 95 Momentary Push Run — Activation starts the motor.
96 97 Momentary Push Stop — Activation stops the motor.
98 99
Forward/Reverse — This setting operates in conjunction with another terminal being set to the Run/Stop (100/101)
function. When configured to Run
(Run/Stop terminal active), the activation or deactivation changes the direction of
the motor.
100 101 Run/StopActivation enables the motor to run and deactivation disables the motor.
102 103
Line Power Bypass — This function operates in conjunction with the Line Power Switching frequency setting
(
F355). An enabled check box at Program

Terminal Selection

Line Power Switching (At) and activation of this
terminal enables this function.
Once configured (including activation of this terminal), the frequency setting of Line Power Switching (Hz)
establishes the speed at which the drive terminates its output and routes commercial power to the motor.
104 105
Frequency Priority — Activation allows for the frequency control to be switched from the frequency command
source selected as Frequency Mode #1 to Frequency Mode #2. This function is enabled by setting the Reference
Priority Selection to Frequency Source Priority Switching and is located at Program Fundamentals Standard
Mode Selection Reference Priority Selection Frequency Source Priority Switching.
106 107
VI/II Terminal Priority — Activation assigns command control to the VI/II Terminal and overrides all other
Terminal Board input so long as the Command Mode is set to Use Terminal Board.
108 109
Command Terminal Board Priority — Activation overrides the FMOD setting and assigns speed control to the
Terminal Board.
110 111
Parameter Editing Enabling — Used with the CN8 Option (LED Keypad) only. Activation enables parameter
editing via the CN8 connector (and keypad).
112 113
Control Switch (torque, position) — Activation allows for a system change from speed to torque or position as a
function of the V/f setting.
114 115
Deviation Counter Clear — Activation clears the Deviation Counter while operating in the Position Control
mode.
116 117
Position Control Forward Limit LS — Activation stops the drive and holds its position. If the connection remains
the drive will time out and trip. This function is normally used for over-travel conditions.
118 119
Position Control Reverse Limit LS — Activation stops the drive and holds its position. If the connection remains
the drive will time out and trip. This function is normally used for over-travel conditions.
120 121
Light-Load High-Speed Operation Enable — Activation sets the lower limit of an output frequency range in
which the Light-Load/High-Speed function may be used (see
F330). The Light-Load/High-Speed function
accelerates the output frequency of the ASD to the speed setting established in F341 for the duration of the activation.
122 123 Snap Stop Control Enable — Not Used.
Note:NO/NC = Normally Open/Normally Closed. NO/NC selection numbers are used when making system changes via
communications.
Table 14.(Continued) Discrete Input Terminal Assignment Selections and Descriptions.
Sel. No.
Terminal Selection Descriptions
NO NC
o
torized Po
t