80 HX7+ ASD Installation and Operation Manual
Preset Speed #3
Program Pattern Run Preset Speeds
This parameter assigns an output frequency to binary number 0011 and is
identified as Preset Speed #3. The binary number is applied to S1S4 of the
Terminal Board to output the Preset Speed (see F018 for further information
on this parameter).
Direct Access Number — F020
Parameter Type — Numerical
Factory Default 0.0
Changeable During Run — Ye s
Minimum — Lower Limit (F013)
Maximum — Upper Limit (F012)
Units — Hz
Preset Speed #4
Program Pattern Run Preset Speeds
This parameter assigns an output frequency to binary number 0100 and is
identified as Preset Speed #4. The binary number is applied to S1S4 of the
Terminal Board to output the Preset Speed (see F018 for further information
on this parameter).
Direct Access Number — F021
Parameter Type — Numerical
Factory Default 0.0
Changeable During Run — Ye s
Minimum — Lower Limit (F013)
Maximum — Upper Limit (F012)
Units — Hz
Preset Speed #5
Program Pattern Run Preset Speeds
This parameter assigns an output frequency to binary number 0101 and is
identified as Preset Speed #5. The binary number is applied to S1S4 of the
Terminal Board to output the Preset Speed (see
F018 for further information
on this parameter).
Direct Access Number — F022
Parameter Type — Numerical
Factory Default 0.0
Changeable During Run — Ye s
Minimum — Lower Limit (F013)
Maximum — Upper Limit (F012)
Units — Hz
Preset Speed #6
Program Pattern Run Preset Speeds
This parameter assigns an output frequency to binary number 0110 and is
identified as Preset Speed #6. The binary number is applied to S1S4 of the
Terminal Board to output the Preset Speed (see F018 for further information
on this parameter).
Direct Access Number — F023
Parameter Type — Numerical
Factory Default 0.0
Changeable During Run — Ye s
Minimum — Lower Limit (F013)
Maximum — Upper Limit (F012)
Units — Hz
Preset Speed #7
Program Pattern Run Preset Speeds
This parameter assigns an output frequency to binary number 0111 and is
identified as Preset Speed #7. The binary number is applied to S1S4 of the
Terminal Board to output the Preset Speed (see F018 for further information
on this parameter).
Direct Access Number — F024
Parameter Type — Numerical
Factory Default 0.0
Changeable During Run — Ye s
Minimum — Lower Limit (F013)
Maximum — Upper Limit (F012)
Units — Hz
Low Speed Signal Output Frequency
Program Terminal Selection Reach Settings
The Low Speed Signal Output Frequency parameter sets a frequency
threshold that activates the assigned output terminal so long as the ASD output
is at or above this setting (see Table 16 on pg. 194 for the available output
assignments).
Direct Access Number — F100
Parameter Type — Numerical
Factory Default 0.0
Changeable During Run — Ye s
Minimum — 0.0
Maximum — Max. Freq. (F011)
Units — Hz
F020 F100