HX7+ ASD Installation and Operation Manual 81
Speed Reach Frequency
Program Terminal Selection Reach Settings
The Speed Reach Frequency sets a frequency threshold that, when reached or 
is within the bandwidth specified by parameter 
F102, will provide a signal at an 
output terminal that can close an appropriately configured output contact (see 
Table 16 on pg. 194 for the available output assignments).
Direct Access Number —  F101
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Ye s
Minimum — 0.0
Maximum — Max. Freq. (F011)
Units — Hz
Speed Reach Frequency Range
Program Terminal Selection Reach Settings
This parameter sets the bandwidth of the Speed Reach Frequency (F101) 
setting.
Direct Access Number —  F102
Parameter Type — Numerical
Factory Default — 2.5
Changeable During Run — Ye s
Minimum — 0.0
Maximum — Max. Freq. (F011)
Units — Hz
F101 F102