3.
System Configuration Unit and Module
29
Communication Base Unit USCB1
USCB1 specifications
Item Specification
Model name USBC1
Form of attachment Exclusively for mounting on DIN rail (fixed in place with M4 screws)
Matching module Up to 2 SBIF1 modules; in single system mounted on left (P) side.
Number connected to main unit Up to 15 can be connected to the serial bus (when SBIF1/SBIF2 module is
used).
Number of PI/Os connected
Up to 14 PI/Os can be connected when single I/O Module is used.
Up to 28 PI/Os can be connected when dual I/O Module is used.
Serial bus terminal block 12-pin removable terminal block (attached with M3.5 screws).
Used for serial bus connection and for receiving system power supply (24
Vdc).
Address setting Set from 1 to F (decimal 1 to 15) by front panel address setting switch.
System power supply
24 Vdc
10% (21.6 to 26.4 V), ripple 5% or less
Maximum current in mounted
modules
24 Vdc-0.3 A (total current consumption of all mounted modules)
Maximum current supply to
I/O bus side
24 Vdc-2.2 A (total PI/O modules current consumption)
Accessories 1 termination connector FSTM1; 1 blank cover FSCV1
External dimensions
80 W
138 H
60 D mm (unit by itself, excluding protrusions)
80 W
138 H
120 D mm (with module mounted, excluding protrusions)
Weight 300 g or less (this unit by itself)
USCB2 specifications
Item Specification
Model name USBC2
Form of attachment Only for horizontal mounting of DIN rails (fixed with specialized stopper
fittings)
Matching module Up to 2 SBIF1 modules; in single system mounted on left (P) side.
Number connected to main unit Up to 15 can be connected to the serial bus (when SBIF1 module is used).
Number of PI/Os connected
Up to 14 PI/Os can be connected when single I/O Module is used.
Up to 28 PI/Os can be connected when dual I/O Module is used.
Serial bus terminal block 12-pin removable terminal block (attached with M3.5 screws).
Used for serial bus connection and for receiving system power supply (24
Vdc).
Address setting Set from 1 to F (decimal 1 to 15) by front panel address setting switch.
System power supply
24 Vdc
10% (21.6 to 26.4 V), ripple 5% or less
Maximum current in mounted
modules
24 Vdc-0.3 A (total current consumption of all mounted modules)
Maximum current supply to
I/O bus side
24 Vdc-2.2 A (total PI/O modules current consumption)
External dimensions
80 W
160 H
15 D mm (unit by itself, excluding protrusions)
80 W
160 H
110 D mm (with module mounted, excluding protrusions)
I/O bus terminating resister Built-in termination resistor
Weight 300 g or less (this unit by itself)

Table of Contents

Other manuals for Toshiba TOSDIC-CIE DS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSDIC-CIE DS and is the answer not in the manual?

Toshiba TOSDIC-CIE DS Specifications

General IconGeneral
BrandToshiba
ModelTOSDIC-CIE DS
CategoryControl Systems
LanguageEnglish

Related product manuals