[6] Speed/torque reference gain/bias setup [2/3] Sensorless vector/PG feedback control (●:Effective, -:Ineffective)
Title
Communi
cation
No.
Function Adjustment range
Minimum
setting unit
(Panel/Communi
cation)
Default
setting
Write during
running
Vector
control
PM
control
V/f Reference
0203 VI/II input point 2 setting 0~100% 1/1 100 Enabled ●/● ● ● 7. 3. 2
0204 VI/II input point 2 frequency 0.0~ Hz 0.1/0.01 *1 Enabled ●/● ● ●
7. 3. 2
0205 VI/II input point 1 rate 0~250% 1/0.01 0 Enabled ●/● - -
7. 3. 2
0206 VI/II input point 2 rate 0~250% 1/0.01 100 Enabled ●/● - -
7. 3. 2
0207 Frequency setting mode selection 2 Same as (1~12) 1/1 1 Disabled ●/● ● ● 6. 6. 1
0208
Speed command priority switching
frequency
0.1~ Hz 0.1/0.01 0.1 Enabled ●/● ● ● 6. 6. 1
0209 Analog input filter
0:No filter
1:Filter approx. 10ms
2:Filter approx. 15ms
3:Filter approx. 30ms
4:Filter approx. 60ms
1/1 0 Enabled ●/● ● ● 7. 2. 3
0210 RR/S4 input point 1 setting 0~100% 1/1 0 Enabled ●/● ● ● 7. 3. 1
0211 RR/S4 input point 1 frequency 0.0~ Hz 0.1/0.01 0.0 Enabled ●/● ● ● 7. 3. 1
0212 RR/S4 input point 2 setting 0~100% 1/1 100 Enabled ●/● ● ● 7. 3. 1
0213 RR/S4 input point 2 frequency 0.0~ Hz 0.1/0.01 *1 Enabled ●/● ● ●
7. 3. 1
0214 RR/S4 input point 1 rate 0~250% 1/0.01 0 Enabled ●/● - -
7. 3. 1
0215 RR/S4 input point 2 rate 0~250% 1/0.01 100 Enabled ●/● - -
7. 3. 1
0216 RX input point 1 setting -100~100% 1/1 0 Enabled ●/● ● ● 7. 3. 3
0217 RX input point 1 frequency 0.0~ Hz 0.1/0.01 0.0 Enabled ●/● ● ● 7. 3. 3
0218 RX input point 2 setting -100~100% 1/1 100 Enabled ●/● ● ● 7. 3. 3
0219 RX input point 2 frequency 0.0~ Hz 0.1/0.01 *1 Enabled ●/● ● ● 7. 3. 3
0220 RX input point 1 rate -250~250% 1/0.01 0 Enabled ●/● - -
7. 3. 3
0221 RX input point 2 rate -250~250% 1/0.01 100 Enabled ●/● - -
7. 3. 3
0222 AI1 input point 1 setting -100~100% 1/1 0 Enabled ●/● ● ● *2
0223 AI1 input point 1 frequency 0.0~ Hz 0.1/0.01 0.0 Enabled ●/● ● ● *2
0224 AI1 input point 2 setting -100-100% 1/1 100 Enabled ●/● ● ● *2
0225 AI1 input point 2 frequency 0.0~ Hz 0.1/0.01 *1 Enabled ●/● ● ● *2
0228 AI2 input point 1 setting 0~100% 1/1 0 Enabled ●/● ● ● *2
0229 AI2 input point 1 frequency 0.0~ Hz 0.1/0.01 0.0 Enabled ●/● ● ● *2
This parameter moves to a fundamental parameter.
*1: Inverter with a model number ending with -WN: 60.0 -WP: 50.0