K-17
E6581386
11
[22] Communication function Sensorless vector/PG feedback control (:Effective, -:Ineffective)
Title
Communi
cation
No.
Function Adjustment range
Minimum
setting unit
(Panel/Communi
cation)
Default
setting
Write during
running
Vector
control
PM
control
V/f Constant
Reference
 0576 IP address setting method
0: Manual setting (~ Enabled)
1: BOOTP
2: DHCP
1/1 0 Enabled / *1
 0577 Data1
0~255 1/1 0 Enabled / *1
 0578 Data2 0~255 1/1 0 Enabled / *1
 0579 Data3 0~255 1/1 0 Enabled / *1
 0580
IP card
Data4 0~255 1/1 0 Enabled / *1
 0581 Data1
0~255 1/1 0 Enabled / *1
 0582 Data2 0~255 1/1 0 Enabled / *1
 0583 Data3 0~255 1/1 0 Enabled / *1
 0584
Subnet mask
Data4 0~255 1/1 0 Enabled / *1
 0585 Data1
0~255 1/1 0 Enabled / *1
 0586 Data2 0~255 1/1 0 Enabled / *1
 0587 Data3 0~255 1/1 0 Enabled / *1
 0588
IP gate1
Data4 0~255 1/1 0 Enabled / *1
 0589 Data1
0~255 1/1 0 Enabled / *1
 0590 Data2 0~255 1/1 0 Enabled / *1
 0591 Data3 0~255 1/1 0 Enabled / *1
 0592
IP master
Data4 0~255 1/1 0 Enabled / *1
 0593 IO scan permission
0: Prohibit
1: Permit
1/1 0 Enabled / *1
 0594
Communication time-out (Modbus)
0.0~60.0sec. 0.1/0.1 0 Enabled / *1
*1:This function is for Etherenet communication option.(planning)
[23] Protection functions [1/4] Sensorless vector/PG feedback control (:Effective, -:Ineffective)
Title
Communi
cation
No.
Function Adjustment range
Minimum
setting unit
(Panel/Communi
cation)
Default
setting
Write during
running
Vector
control
PM
control
V/f Constant
Reference
 0601 Stall prevention level 10~164%, 165:Deactivated 1/1 120 Enabled / 6. 26. 1
 0602 Inverter trip record retention selection
0:Clear when power is turned off
1:Retain even after power is turned off
1/1 0 Enabled / 6. 26. 2
 0603 Emergency stop
0:Coast stop
1:Deceleration stop
2:Emergency DC braking
1/1 0 Disabled / 6. 26. 3
 0604 Emergency DC braking control time 0.0~20.0 sec. 0.1/0.1 1.0 Enabled / 6. 26. 3
 0605
Output phase failure detection mode
selection
0:Deselect
1:At starting (only one time after power is turned
on)
2:At starting (each time power is turned on)
3:During operation
4:At starting + during operation
5:Output cut-off detection enabled
1/1 0 Disabled / 6. 26. 4

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-PS1 and is the answer not in the manual?

Toshiba TOSVERT VF-PS1 Specifications

General IconGeneral
BrandToshiba
ModelTOSVERT VF-PS1
CategoryPower Supply
LanguageEnglish

Related product manuals