K-19
E6581386
11
[23] Protection functions [3/4] Sensorless vector/PG feedback control (●:Effective, -:Ineffective)
Title
Communi
cation
No.
Function Adjustment range
Minimum
setting unit
(Panel/Communi
cation)
Default
setting
Write during
running
Vector
control
PM
control
V/f Constant
Reference
0634
Annual average ambient temperature
(calculation for part replacement alarms)
1:-10~+10°C
2:+11~+20°C
3:+21~+30°C
4:+31~+40°C
5:+41~+50°C
6:+51~+60°C
1/1 3 Enabled ●/● ● ● 6. 26. 17
0635
Rush current suppression relay activation
time
0.0~2.5 sec. 0.1/0.1 0.0 Disabled ●/● ● ● 6. 26. 18
0637 PTC1 thermal selection
0:Deselect
1:Select
1/1 0 Disabled ●/● ● ● *1
0638 PTC2 thermal selection
0:Deselect
1:Select
1/1 0 Disabled ●/● ● ● *1
0639
Braking resistance overload time (10 times
of rated torque)
0.1~600.0 sec. 0.1/0.1 5.0 Disabled ●/● ● ● 5. 19
0640
Step-out detection current level (for PM
motors)
10~150 1/1 100 Disabled - ● - 6. 24
0641 Step-out detection time (for PM motors)
0.0:Not detect
0.1~25.0
0.1/0.1 0.0 Disabled - ● - 6. 24
0643
Brake-equipped motor restart condition
selection
0:Default (no waiting time for frequencies of 10Hz
and less)
1:Conditional (no waiting time for frequencies of
20Hz and less)
1/1 0 Disabled ●/● ● ● 6. 26. 21
0644
Action in the event of VI/II analog input wire
breakage
0:Trip mode
1: The inverter operates the motor at preset speed
operation frequency 14.
1/1 0 Disabled ●/● ● ● 6. 26. 16
0645 PTC thermal selection
0:Disabled
1:Enabled (trip mode)
2:Enabled (alarm mode)
1/1 0 Disabled ●/● ● ● 6. 26. 22
0646 PTC detection resistor value 100-9999 1/1 3000 Disabled ●/● ● ● 6. 26. 22
*1: For details, refer to Instruction Manual (E6581339) specified in Section 6.36.