K-20
E6581386
11
[23] Protection functions [4/4] Sensorless vector/PG feedback control (:Effective, -:Ineffective)
Title
Communi
cation
No.
Function Adjustment range
Minimum
setting unit
(Panel/Communi
cation)
Default
setting
Write during
running
Vector
control
PM
control
V/f Constant
Reference
 0647
Control power supply backup option failure
monitoring
0:Control power supply not backed up
1:Control power supply backed up (alarm in the
event of a failure)
2:Control power supply backed up (tripping in the
event of a failure)
1/1 0 Disabled / 6. 26. 23
 0650 Forced fire-speed control selection 0:Disabled, 1:Enabled 1/1 0 Enabled / 6. 27
 0651 Undertorque detection selection 0:Alarm mode, 1:Trip mode 1/1 0 Enabled / 6. 28
 0652
Undertorque detection level during power
running
0~250% 1/0.01 0 Enabled / 6. 28
 0653
Undertorque detection level during
regenerative braking
0~250% 1/0.01 0 Enabled / 6. 28
 0654 Undertorque detection time 0.00~10.00 sec. 0.01/0.01 0.50 Enabled / 6. 28
 0655 Undertorque detection hysteresis 0~100% 1/0.01 10 Enabled / 6. 28
[24] Override Sensorless vector/PG feedback control (:Effective, -:Ineffective)
Title
Communi
cation
No.
Function Adjustment range
Minimum
setting unit
(Panel/Communi
cation)
Default
setting
Write during
running
Vector
control
PM
control
V/f Constant
Reference
 0660 Override addition input selection
0:Disabled
1:VI/II (voltage/current input)
2:RR/S4 (potentiometer/voltage input)
3:RX (voltage input)
4:Operation panel input enabled (including
LED/LCD option input)
5:2-wire RS485 input enabled
6:4-wire RS485 input enabled
7:Communications option input enabled
8:Optional AI1 (differential current input)
9:Optional AI2 (voltage/current input)
10:UP/DOWN frequency
11:Optional RP pulse input
12:Optional high-speed pulse input
13:-
1/1 0 Enabled / 6. 29
 0661 Override multiplication input selection
0:Disabled
1:VI/II
2:RR/S4
3:RX
4: -
5:Optional AI1
1/1 0 Enabled / 6. 29
 0669 Logic output/pulse output selection (OUT1) 0:Logic output, 1:Pulse output 1/1 0 Disabled / 6. 30. 1
 0670 AM terminal meter selection 0~64 *1 1/1 2 Enabled / 5. 16
This parameter moves to a fundamental parameter. *1: For the adjustment range, see the table on page K-35.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-PS1 and is the answer not in the manual?

Toshiba TOSVERT VF-PS1 Specifications

General IconGeneral
BrandToshiba
ModelTOSVERT VF-PS1
CategoryPower Supply
LanguageEnglish

Related product manuals