K-27
E6581386
11
[27] Communication function [3/5] Sensorless vector/PG feedback control (●:Effective, -:Ineffective)
Title
Communi
cation
No.
Function Adjustment range
Minimum
setting unit
(Panel/Communi
cation)
Default
setting
Write during
running
Vector
control
PM
control
V/f Constant
Reference
0825 Send waiting time (4-wire RS485) 0.00:Default, 0.01~2.00 sec. 0.01/0.01 0.00 Enabled ●/● ● ● 6. 34. 1
0826
Inverter-to-inverter communication setting
(4-wire RS485)
0:Slave (issues a 0Hz command if something goes
wrong with the master)
1:Slave (continues operation if something goes
wrong with the master)
2:Slave (trips for emergency stop if something
goes wrong with the master)
3:Master (sends a frequency command)
4:Master (sends an output frequency)
5: -
6: -
1/1 0 Enabled ●/● ● ● 6. 34. 1
0829 Protocol selection (4-wire RS485)
0:TOSHIBA
1:MODBUS
1/1 0 Enabled ●/● ● ● 6. 34. 1
0830
Communication option setting 1
0~7 1/1 0 Enabled ●/● ● ● *1
0831
Communication option setting 2
0000~ 1/1 0000 Enabled ●/● ● ● *1
0832
Communication option setting 3
0000~ 1/1 0000 Enabled ●/● ● ● *1
0833
Communication option setting 4
0000~ 1/1 0000 Enabled ●/● ● ● *1
0834
Communication option setting 5
0000~ 1/1 0000 Enabled ●/● ● ● *1
0835
Communication option setting 6
0000~ 1/1 0000 Enabled ●/● ● ● *1
0836
Communication option setting 7
0000~ 1/1 0000 Enabled ●/● ● ● *1
0837
Communication option setting 8
0000~ 1/1 0000 Enabled ●/● ● ● *1
0838
Communication option setting 9
0000~ 1/1 0000 Enabled ●/● ● ● *1
0841
Communication option setting 10
0000~ 1/1 0000 Enabled ●/● ● ● *1
0842
Communication option setting 11
0000~ 1/1 0000 Enabled ●/● ● ● *1
0843
Communication option setting 12
0000~ 1/1 0000 Enabled ●/● ● ● *1
0844
Communication option setting 13
0000~ 1/1 0000 Enabled ●/● ● ● *1
0845
Communication option setting 14
0000~ 1/1 0000 Enabled ●/● ● ● *1
0846
Communication option setting 15
0000~ 1/1 0000 Enabled ●/● ● ● *1
0847
Communication option setting 16
0000~ 1/1 0000 Enabled ●/● ● ● *1
0848
Communication option setting 17
0000~ 1/1 0000 Enabled ●/● ● ● *1
0849
Communication2 time-out
condition selection
0:Disconnection detection
1:When communication mode enable
2:1+Driving operation
1/1 0 Enabled ●/● ● ● *1
0850 Disconnection detection extended time 0.0~100.0 sec. 0.1/0.1 0.0 Enabled ●/● ● ● *1
0851 Inverter operation at disconnection
0:Inverter stop, communication command,
frequency mode open (by , )
1:None (continued operation)
2:Deceleration stop
3:Coast stop
4:Network error ( trip)
5:Preset speed operation (by setting)
1/1 0 Enabled ●/● ● ● *1
0852 Preset speed operation selection
0:None
1~15:Preset speed operation (by parameter
setting)
1/1 0 Enabled ●/● ● ● *1
*1: For details, refer to Instruction Manual (E6581281, E6581343) specified in Section 6.36.