K-17
E6581386
11
[22] Protection functions [1/3] Sensorless vector/vector with sensor (:Effective, -:Ineffective)
Title
Communi
cation
No.
Function Adjustment range
Minimum
setting unit
(Panel/Communi
cation)
Default
setting
Write during
running
Vector
control
PM
control
V/f Constant
Reference
 0601 Stall prevention level 0~164%, 165:Deactivated 1/1 120 Enabled /●●6. 26. 1
 0602 Inverter trip record retention selection
0:Clear when power is turned off
1:Retain even after power is turned off
1/1 0 Enabled /●●6. 26. 2
 0603 Emergency stop
0:Coast stop
1:Deceleration stop
2:Emergency DC braking
1/1 0 Disabled /●●6. 26. 3
 0604 Emergency DC braking control time 0.0~20.0 sec. 0.1/0.1 1.0 Enabled /●●6. 26. 3
 0605
Output phase failure detection mode
selection
0:Deselect
1:At starting (only one time after power is turned
on)
2:At starting (each time power is turned on)
3:During operation
4:At starting + during operation
5:Output cut-off detection enabled
1/1 0 Disabled /●●6. 26. 4
 0606 OL reduction starting frequency 0.0~60.0Hz 0.1/0.01 6.0 Enabled /●●5. 14
 0608 Input phase failure detection mode selection
0:Disabled
1:Enabled
1/1 1 Disabled /●●6. 26. 6
 0609 Low current detection hysteresis width 1~20% 1/1 10 Enabled /●●6. 26. 7
 0610 Low current trip selection
0:No trip
1:Trip
1/1 0 Enabled /●●6. 26. 7
 0611 Low current detection current 0~100% 1/1 0 Enabled /●●6. 26. 7
 0612 Low current detection time 0~255 sec. 1/1 0 Enabled /●●6. 26. 7
 0613 Selection of short circuit detection at starting
0:Each time (standard pulse)
1:Only one time after power is turned on
2:Each time (short pulse)
3.Only one time after power is turn on (short
pulse)
4:Each time (Extremely shot-time pulse)
5.Only one time after power is turn on (Extremely
shot-time pulse)
1/1 0 Disabled /●●6. 26. 8
 0615 Overtorque trip selection
0:No trip
1:Trip
1/1 0 Enabled /●●6. 26. 9
 0616
Overtorque detection level during power
running
0~250% 1/0.01 150 Enabled /●●6. 26. 9
 0617
Overtorque detection level during
regenerative braking
0~250% 1/0.01 150 Enabled /●●6. 26. 9
 0618 Overtorque detection time 0.00~10.00 sec. 0.01/0.01 0.50 Enabled /●●6. 26. 9
 0619 Overtorque detection hysteresis 0~100% 1/0.01 10 Enabled /●●6. 26. 9