4.3.1 Adjustment of the start and end point via two separate inputs
Set the Start-Point:
- Displacement of the position sensor (permanent magnet) to the desired start
position.
- Connecting the input “Start point" to 24 VDC ±10%, >200 ms.
- Position is saved and the lowest analog value is output.
Set the End-Point:
- Displacement of the position sensor (permanent magnet) to the desired end
position.
- Connecting the input "End point" to 24 VDC ±10%, >200 ms.
- Position is saved and the highest analog value is output.
4.3.2 Timed adjustment of the start and end point via one input
Set the Start-Point:
- Displacement of the position sensor (permanent magnet) to the desired start
position.
- Connecting the input “Start point" to 24 VDC ±10% for between 50 ms and 3 s.
- Position is saved and the lowest analog value is output.
Set the End-Point:
- Displacement of the position sensor (permanent magnet) to the desired end
position.
- Connecting the input "End point" to 24 VDC ±10% for >3 s.
- Position is saved and the highest analog value is output.