EasyManua.ls Logo

Trane Sintesis RTAF - Page 83

Trane Sintesis RTAF
92 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Diagnostics
RTAF-SVX001A-EN 83
Comm Loss: Heat
Recovery Leaving Water
Temperature Sensor
Comm Loss: HR Leaving
Water Temp Sensor
Comm: HR Leaving Water
Temp
Chiller Info Latch All
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Remote
Comm Loss: High
Pressure Cutout Switch -
xy
Comm Loss: High
Pressure Cutout Sw - xy
Comm: High Pres Cutout
Sw - xy
Cprsr Normal Latch All
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Remote
Comm Loss: Liquid Line
Temperature
Comm: Liquid Line Temp
Circuit Normal Latch All
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period Note: The
Subcooled Liquid Line Temperature Sensors are used for
determination of charge and accurate tonnage predictions
Remote
Comm Loss: Local BAS
Interface
Comm: Local BAS
Interface
Chiller Info NonLatch All
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Use last valid BAS setpoints.
Diagnostic is cleared when successful communication is
established with the LonTalk LLID (LCIC) or BacNet LLID
(BCIC).
Remote
Comm Loss: Motor RLA
Input - xA
Comm: Motor RLA Input -
xA
Cprsr Normal Latch All
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Remote
Comm Loss: Motor
Winding Thermostat
Compressor 1A
Comm Loss: Motor
Winding Tstat Cprsr 1A
Comm: Motor Tstat Cprsr
1A
Circuit Normal Latch All
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Remote
Comm Loss: Motor
Winding Thermostat
Compressor 2A
Comm Loss: Motor
Winding Tstat Cprsr 2A
Comm: Motor Tstat Cprsr
2A
Circuit Normal Latch All
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Remote
Comm Loss: Oil Loss Level
Sensor Input
Comm Loss: Oil Loss Level
Sensor Input
Comm: Oil Level Sensor
Circuit Normal Latch All
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Remote
Comm Loss: Oil Pressure -
xy
Comm: Oil Pressure - xy
Cprsr Immediate Latch All
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Remote
Comm Loss: Oil Return
Line Solenoid Valve -xy
Comm Loss: Oil Return
Solenoid Valve - xy
Comm: Oil Ret Sol Vlv xy
Cprsr Normal Latch All
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Remote
Comm Loss: Outdoor Air
Temperature
Comm: Outdoor Air Temp
Chiller Normal Latch All
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Remote
Comm Loss:
Programmable Relay
Board 1
Comm: Program Relay
Board 1
None Info Latch All
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Remote
Table 28. Communications diagnostics (continued)
Diagnostic Name
Affects
Target Severity Persistence
Active
Modes
[Inactive
Modes] Criteria
Reset
Level

Table of Contents

Related product manuals