CHAPTER 19 - PRODUCT SPECIFICATIONS
Boiler
Model
Fuel Input
DOE
Heating Capacity
Net AHRI
Rating
AFUE
Shipping
Weight
Lbs / Kg
Solo 80
Natural
Propane
16,000 -
80,000
74,000 64,000 95% 103 / 47
Solo 110
Natural
Propane
20,000 -
110,000
102,000 89,000 95% 103 / 47
Solo 155
Natural
Propane
27,800 -
153,000
142,000 123,000 95% 118 / 53.5
Solo 175
Natural
Propane
30,900 -
170,000
157,000 137,000 95% 128 / 58
Solo 250
Natural
Propane
43,600 -
240,000
222,000 193,000 95% 140 / 63.5
Solo 299
Natural
Propane
72,500 -
299,000
278,000 242,000 95% 210 / 95
Boiler
Model
Fuel Input Output
Net AHRI
Rating
Combustion
Eciency
Thermal
Eciency
Shipping
Weight
Lbs / Kg
Solo 399
Natural
Propane
72,500 -
399,000
379,000 330,000 94.1% 95.1% 216 / 98
• The heating capacity of the PRESTIGE Solo 80/110/155/175/250/299 is based
on the test requirements of the U.S. Department of Energy.
• The AHRI rating is based on a piping and pick up allowance of 1.15. This al-
lowance should be sufficient for standard radiation requirements.
• Based on the given AFUE the PRESTIGE Solo 80/110/155/175/250/299 meets
the energy efficiency guidelines established by Energy Star.
• Input and output ratings are shown for sea level applications. The PRESTIGE
Solo automatically derates the input at approximately 2% for every 1,000 Ft.
of altitude. No alterations to the boiler or burner system are required.
• PRESTIGE Solo 399 output rating is based off of the thermal efficiency.
NOTICE