EasyManuals Logo

TriangleTube Instinct Series Installation & Maintenance Manual

TriangleTube Instinct Series
112 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #108 background imageLoading...
Page #108 background image
96
CHAPTER 19
CHAPTER 19 - PRODUCT SPECIFICATIONS
0
2
4
6
8
10
12
14
16
456789 10 11 12
Pressure Drop (Ft. W.C.)
Flow Rate (GPM)
Pressure Drop Comparison - Taco
Solo 80 Solo 110 Taco 005 Taco 007 Taco 0010 Taco 0012
0
2
4
6
8
10
12
14
16
456789 10 11 12
Pressure Drop (Ft. W.C.)
Flow Rate (GPM)
Pressure Drop Comparison - Grundfos
Solo 80 Solo 110
Grundfos UPS15-58F/FC - Spd 1 Grundfos UPS15-58F/FC - Spd 2
Grundfos UPS15-58F/FC - Spd 3
Graph 1 - Pressure Loss Through Boiler - Taco Circulators
Note: Minimum allowable ow rate at full input:
- 4 gpm SOLO 80
- 5 gpm SOLO 110
Graph 2 - Pressure Loss Through Boiler - Grundfos Circulators