96
CHAPTER 19
CHAPTER 19 - PRODUCT SPECIFICATIONS
0
2
4
6
8
10
12
14
16
456789 10 11 12
Pressure Drop (Ft. W.C.)
Flow Rate (GPM)
Pressure Drop Comparison - Taco
Solo 80 Solo 110 Taco 005 Taco 007 Taco 0010 Taco 0012
0
2
4
6
8
10
12
14
16
456789 10 11 12
Pressure Drop (Ft. W.C.)
Flow Rate (GPM)
Pressure Drop Comparison - Grundfos
Solo 80 Solo 110
Grundfos UPS15-58F/FC - Spd 1 Grundfos UPS15-58F/FC - Spd 2
Grundfos UPS15-58F/FC - Spd 3
Graph 1 - Pressure Loss Through Boiler - Taco Circulators
Note: Minimum allowable ow rate at full input:
- 4 gpm SOLO 80
- 5 gpm SOLO 110
Graph 2 - Pressure Loss Through Boiler - Grundfos Circulators