112
CHAPTER 19
CHAPTER 19 - PRODUCT SPECIFICATIONS
Graph 1 - INSTINCT Solo - Pressure Loss Through Boiler
Note: Minimum allowable ow rate at full input:
- 5 gpm SOLO 110
- 7gpm SOLO 155
- TBC SOLO 199
Pressure Drop Instinct Solo
0
2
4
6
8
10
12
14
16
4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Pressure Drop (Ft. W.C.)
Flow Rate (GPM)
Pressure Drop Ion-ic Solo
Ion-ic Solo 110/155/199
Pressure Drop (Ft. W.C.)
Flow Rate (GMP)
INSTINCT Solo 110/155