EasyManua.ls Logo

turck TBEN-L 8IOL Series - Page 100

turck TBEN-L 8IOL Series
148 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Commissioning
Commissioning the device in EtherNet/IP™
100
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
Attr. no. Designation Get/
set
Type Meaning
Dec. Hex.
16 0x10 Hardware error G USINT 0 = inactive
1 = active
17 0x11 Maintenance events G USINT 0 = inactive
1 = active
18 0x12 Out-of-specification
events
G USINT 0 = inactive
1 = active
19 0x13 Parameterization error G USINT 0 = inactive
1 = active
20 0x14 Over temperature G USINT 0 = inactive
1 = active
21 0x15 Lower limit value un-
derrun
G USINT 0 = inactive
1 = active
22 0x16 Upper limit value ex-
ceeded
G USINT 0 = inactive
1 = active
23 0x17 Undervoltage G USINT 0 = inactive
1 = active
24 0x18 Overvoltage G USINT 0 = inactive
1 = active
25 0x19 Overload G USINT 0 = inactive
1 = active
26 0x1A Common error G USINT 0 = inactive
1 = active
27 0x1B Port parameterization
error
G USINT 0 = inactive
1 = active
Process data
28 0x1C Input data word 0 G USINT
G USINT
43 0x2B Input data word 15 G USINT
44 0x2C Output data word 0 G USINT
G USINT
59 0x3B Output data word 15 G USINT

Table of Contents