V02.00 | 2019/10
101
IO-Link Events Class (VSC 138)
Attr. no. Designation Get/Set Type Meaning
Dec. Hex.
1 0x01 IOL-Event 1 – port G USINT Port no. of the port which sends the
1st IO-Link Event.
… …
16 0x10 IOL-Event 16 –
port
G USINT Port no. of the port which sends the
16th IO-Link Event.
17 0x11 IOL-Event 1 –
qualifier
G USINT Qualifier of the 1st IO-Link event
… …
32 0x20 IOL-Event 16 –
qualifier
G USINT Qualifier of the 1st IO-Link event
33 0x21 IOL-Event 1–
Event Code
G USINT Event code of the 1st IO-Link event
… …
48 0x30 IOL-Event 16–
Event Code
G USINT Event code of the 1st IO-Link event
Basic Class (VSC 153)
Attr. no. Designation Get/
Set
Type Meaning
Dec. Hex.
1 0x01 DXP 1 - Manual output reset after overcurrent G/S USINT 0 = no
1 = yes
2 0x02 DXP 3 - Manual output reset after overcurrent G/S USINT 0 = no
1 = yes
3 0x03 DXP 5 - Manual output reset after overcurrent G/S USINT 0 = no
1 = yes
4 0x04 DXP 7 - Manual output reset after overcurrent G/S USINT 0 = no
1 = yes
5 0x05 DXP 1 - Activate output G/S USINT 0 = no
1 = yes
6 0x06 DXP 3 - Activate output G/S USINT 0 = no
1 = yes
7 0x07 DXP 5 - Activate output G/S USINT 0 = no
1 = yes
8 0x08 DXP 7 - Activate output G/S USINT 0 = no
1 = yes
9 0x09 DXP 1 - Overcurrent output G USINT 0 = inactive
1 = active
10 0x0A DXP 3 - Overcurrent output G USINT 0 = inactive
1 = active
11 0x0B DXP 5 - Overcurrent output G USINT 0 = inactive
1 = active
12 0x0C DXP 7 - Overcurrent output G USINT 0 = inactive
1 = active